Figure 20: Example of a Schedule Tolerance Window
The Schedule Tolerance Window applies to Access Schedules only
(see section 15.6 on page 36). and not to the Arming and Disarming
Report Schedules (see section 9.3.1 on page 23).
15.10 Door Access Mode
SECTION [2251] TO [2282]: OPTION [1]
Access Door and user can be assigned to one or more partitions in the
security system. Actions performed by the user will be directly linked to the
partition(s) assigned to that door. Doors 01 to 32 are programmed in
sections [2251] to [2282] respectively.
15.11 Code Access
SECTION [2251] TO [2282]: OPTION [2]
Code Access can allow access to an Access Door by entering a valid user
access code and pressing the [
ACC] key on a EVO641 LCD Keypad instead
of using the Access Card. The control panel will verify its assigned Access
Level and Schedule. Doors 01 to 32 are programmed in sections [2251] to
[2282] respectively.
This option is not available for LED and Grafica Keypads.
15.12 Card and Code Access
SECTION [2251] TO [2282]: OPTION [3]
The Access Door can be programmed to require a user to present a valid
Access Card and then enter the user’s valid code on a DGP-R915 that is
connected to an Access Control Module (DGP-ACM12). The DGP-R915
and the Access Control Module must be correctly configured. Please refer
to the DGP-R915 “Installation and Operating Instructions”, and to the
Access Control Module “Reference & Installation Manual” for instructions.
Doors 01 to 32 are programmed in sections [2251] to [2282] respectively.
When option [3] is enabled, the Access Card must be presented
before the user access code is entered.
15.13 Skip Exit Delay When Arming With Access Card
SECTION [3038]: OPTION [6]
(default = disabled) When arming with an Access Card, the system can
arm with or without starting the Exit Delay.
15.14 Restrict Arming on Door
SECTION [2251] TO [2282]: OPTION [4]
With option [4] ON, the control panel can prevent an Access Card from
arming the partition(s) assigned to the door even if the Access Card is
programmed to permit arming.
15.15 Restrict Disarming on Door
SECTION [2251] TO [2282]: OPTION [5]
With option [5] ON, the control panel can prevent an Access Card from
disarming the partition(s) assigned to the door even if the Access Card is
programmed to permit disarming.
15.16 Door Access During Clock Loss
SECTION [3038]: OPTION [8]
(default = disabled) If the system registers a Clock Loss Trouble, the
control panel will no longer recognize the Schedules until the clock is reset.
Enable or disable the option as required:
15.17
Burglar Alarm On Forced Door or Door Left Open
SECTION [3038]: OPTION [5] (FORCED DOOR)
S
ECTION [3038]: OPTION [7] (DOOR LEFT OPEN)
(default = disabled) If an Access Door is forced open or left open, a signal
can be sent to the control panel to trigger the burglar alarm. The burglar
alarm is generated instantly regardless of the zone’s definition.
For these features to function:
Install a door contact and connect it to the door’s Access Control Module
Assign the Access Control Module to a zone (see Zone Programming on
page 9)
Enable option [5] in section [3038]: Burglar Alarm on Forced Door
Enable option [7] in section [3038]: Burglar Alarm on Door Left Open
15.18 Logging Access Control Events
15.18.1 Log Request For Exit In Event Buffer
SECTION [3038]: OPTION [2]
(default = disabled) When enabled, the control panel can record the REX
events generated from all the Doors in the Event Buffer, but cannot report
these events to the monitoring station. The events can be viewed by
entering the Event Record Display.
Since REX events can occur often, the Event Buffer may fill up quickly.
15.18.2 Log Door Left Open Restore In Event Buffer
SECTION [3038]: OPTION [3]
(default = disabled) When enabled, the Door Left Open Restore event can
be recorded in the Event Buffer. These events cannot be reported to the
monitoring station, but can be viewed by entering the Event Record Display.
15.18.3 Log Door Forced Open Restore In Event Buffer
SECTION [3038]: OPTION [4]
(default = disabled) When enabled, the Door Forced Open Restore event
can be recorded in the Event Buffer. This event cannot be reported to the
monitoring station, but it can be viewed by entering the Event Record
Display.
[1] ON
“OR” Access Door
The Access Door grants access or permits arming or
disarming to users assigned to at least one of the door’s
partitions. An “OR” door will arm or disarm only the
partitions that it has in common with the users.
[1] OFF
“AND” Access Door
The Access Door grants access or permits arming only to
users assigned to all the door’s assigned partitions.
[2] ON [ACC] key enabled
[2] OFF Access with Card only
[3] ON Access Card AND User Access Code required
[3] OFF Access Card OR User Access Code
[6] ON The Exit Delay is cancelled
[6] OFF The Exit Delay is triggered
User’s assigned Schedule is 9a.m. to 5p.m. When ‘Add Tolerance Windows to
Schedules’ is enabled for the user, the user has access from 8a.m. to 6p.m.
Schedule Tolerance Windows
Option Until the Clock is reset, access can be granted to:
[8] ON
The System Master or User Access Code with Master
feature or Schedule 00 (00 = all times) enabled
[8] OFF All users regardless of their programmed Schedules