DIGIPLEXNE CONTROL PANEL 21
7 ALARM OPTIONS
7.1 BELL/ALARM OUTPUT
(Default = only option [1] enabled) When an alarm condition is detected in a
partition, the control panel can toggle the on-board
BELL output enabling
any bells or sirens connected to it. In section [3032] enable the option to
enable the bell output in the desired partition (off = disabled):
7.2 BELL CUT-OFF TIMER
(Default = 004) After an audible alarm, the bell or siren will stop once the
partition is disarmed or when the Bell Cut-Off Timer has elapsed. Enter any
value between 001 and 255 minutes:
7.2.1 No Bell Cut-Off on Fire Alarm
SECTION [3030]: OPTION [2]
(Default = disabled) The control panel can disable the Bell Cut-Off Timers
when alarms are generated from zones defined as Standard or Delayed
Fire Zones (see section 4.3). The
BELL output will remain enabled until a
user disarms the partition in alarm.
7.2.2 Recycle Alarm Rate
(Default = 000) The control panel re-verifies the zone status during an
alarm at a programmed rate once the Bell Cut-Off Timer and the Recycle
Delay elapse. If open zones remain, the control panel will regenerate the
alarm. Enter the number of times from 001 to 255 (000 = no limit) in one
armed period that the control panel will re-verify the zone status:
7.2.3 Recycle Delay
(Default = 000) The Recycle Delay is the amount of time the control panel
will wait after the Bell Cut-off occurs before re-verifying the zone status.
Program the Recycle Delay from 001 to 255 minutes (000 = disabled):
7.3 WIRELESS TRANSMITTER SUPERVISION OPTIONS
S
ECTION [3034]: OPTIONS [1] AND [2]
When the control panel detects a Supervision Loss (wireless receiver no
longer receiving signals from a wireless transmitter), the control panel can
generate an alarm and/or trouble, as shown in the table below, unless the
Wireless Transmitter Supervision Option is disabled.
The Supervision feature must be enabled in the Omnia Wireless
System (OMN-RCV3) for this feature to function.
7.3.1 Supervision Bypass Options
SECTION [3034]: OPTION [3]
(Default = disabled) With option [3] enabled in section [3034], the Wireless
Transmitter Supervision Options will follow the zone's bypass definition.
This means that the control panel will not perform any action if a
supervision loss occurs on a bypassed zone. With option [3] disabled, the
control panel will ignore the bypass definition and will follow the option set
in section 7.3 if a supervision loss occurs on a bypassed zone.
7.4 POLICE CODE TIMER
(Default = 000) If an alarm condition occurs on a zone, the control panel
generates an alarm and triggers the Police Code Timer. The Police Code
Timer requires confirmation of the alarm situation within the delay before
sending the Police Code programmed in [3934]. The Police Code will only
be sent if one of the following conditions occurs during the delay:
1) An alarm occurs on another zone.
2) The zone in alarm restores and reoccurs.
Key in the desired 3-digit delay value (001 to 255 minutes, 000 = disabled)
into the section corresponding to the desired partition:
7.5 TAMPER RECOGNITION OPTIONS
S
ECTION [3034]: OPTIONS [5] AND [6]
When the control panel detects a tamper or wire fault on a zone or on an
expansion module, the control panel can generate an alarm and/or trouble,
as shown in the table below, unless the Tamper Recognition Option is
disabled.
Partition 1: Option [1] Partition 5: Option [5]
Partition 2: Option [2] Partition 6: Option [6]
Partition 3: Option [3] Partition 7: Option [7]
Partition 4: Option [4] Partition 8: Option [8]
Partition 1: [3113] Partition 3: [3313] Partition 5: [3513] Partition 7: [3713]
Partition 2: [3213] Partition 4: [3413] Partition 6: [3613] Partition 8: [3813]
Partition 1: [3117] Partition 3: [3317] Partition 5: [3517] Partition 7: [3717]
Partition 2: [3217] Partition 4: [3417] Partition 6: [3617] Partition 8: [3817]
Partition 1: [3116] Partition 3: [3316] Partition 5: [3516] Partition 7: [3716]
Partition 2: [3216] Partition 4: [3416] Partition 6: [3616] Partition 8: [3816]
Option
Description
[1] [2]
OFF OFF
Disabled (Default):
Displays zone open on the keypads, but will not generate an
alarm or trouble.
Not permitted on UL systems.
OFF ON
Generates Trouble Only (when armed or disarmed):
The control panel displays Zone Fault in the Trouble Display
and transmits the defined report code (see section 8.2).
ON OFF
When disarmed: Generates Trouble Only
The control panel displays Zone Fault in the Trouble Display
and transmits the defined report code (see section 8.2).
When armed: Follows Zone Alarm Type
The control panel follows the zone’s alarm type (see section
4.5.5 on page 15).
ON ON
When disarmed: Generates Audible Alarm
The control panel displays Zone Fault in the Trouble Display,
transmits the defined report code (see section 8.2), and
generates an audible alarm.
When armed: Follows Zone Alarm Type
The control panel follows the zone’s alarm type (see section
4.5.5 on page 15).
Partition 1: [3118] Partition 3: [3318] Partition 5: [3518] Partition 7: [3718]
Partition 2: [3218] Partition 4: [3418] Partition 6: [3618] Partition 8: [3818]
Option
Description
[5] [6]
OFF OFF
Disabled (Default):
Displays zone open on the keypads, but will not generate an
alarm or trouble.
Not permitted on UL systems.
OFF ON
Generates Trouble Only (when armed or disarmed):
The control panel displays Zone Fault in the Trouble Display and
transmits the defined report code (see section 8.2).
ON OFF
When disarmed: Generates Trouble Only
The control panel displays Zone Fault in the Trouble Display and
transmits the defined report code (see section 8.2).
When armed: Follows Zone Alarm Type
The control panel follows the zone’s alarm type (see section
4.5.5 on page 15).
ON ON
When disarmed: Generates Audible Alarm
The control panel displays Zone Fault in the Trouble Display,
transmits the defined report code (see section 8.2), and
generates an audible alarm.
When armed: Follows Zone Alarm Type
The control panel follows the zone’s alarm type (see section
4.5.5 on page 15).